CAD-I-S Rev H
Installation & Service Manual
Models: 40 - 120
This manual must only be used by
a qualified heating installer / service
technician. Read all instructions,
in this manual before installing.
Perform steps in the order given.
Failure to comply could result in
severe personal injury, death, or
substantial property damage.
WARNING
Save this manual for future reference.
Vedere la pagina 0
1 2 3 4 5 6 ... 91 92

Sommario

Pagina 1 - Models: 40 - 120

CAD-I-S Rev H Installation & Service ManualModels: 40 - 120This manual must only be used by a qualified heating installer / service technician.

Pagina 2 - Contents

Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe personal injury or death. WARNINGWhe

Pagina 3 - Please read before proceeding

When removing a boiler from existing common vent system:Do not install the Cadet heating boiler into a common vent with any other appliance. This wil

Pagina 4

2 Prepare boiler12Remove boiler from wood pallet1. After removing the outer shipping carton from the boiler, remove the parts box.2. To remove the

Pagina 5 - Models 40 - 120

Do not drop the boiler. Damage to the boiler can result.REMOVE SHIPPING[WALL] BRACKETDO NOT DISCARD-WILL BE NEEDED TOSECURE THE BOILERTO THE WALLIMG0

Pagina 6 - LOW LEAD CONTENT

3 General ventingIMG00267IMG00219Figure 3-1 Two-Pipe Sidewall Termination - See page 22 for more detailsFigure 3-2 PVC/CPVC Concentric Sidewall Termi

Pagina 7

153 General venting (continued) Installation & Service ManualThis appliance requires a special venting system. Use only approved PVC, CPVC,

Pagina 8

3 General venting 16 Installation & Service Manual Minimum / Maximum allowable combustion air and vent piping lengths are as follows:Combust

Pagina 9

17 Installation & Operation ManualMaterialsAir inlet pipe materials:The air inlet pipe(s) must be sealed. Choose acceptable combustion air i

Pagina 10 - 1 Determine boiler location

Air contamination Pool and laundry products and common household and hobby products often contain fluorine or chlorine compounds. When these chemical

Pagina 11 - (continued)

193 General venting (continued) Installation & Service Manual PVC/CPVC:VENTAIRIMG00225Figure 3-7 Near Boiler PVC/CPVC Venting For models 40

Pagina 12 - 2 Prepare boiler

2Hazard definitionsThe following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or

Pagina 13 - 2 Prepare boiler (continued)

20 Installation & Service Manual The installer must use a specific vent starter adapter at the flue collar connection, supplied by the vent m

Pagina 14 - 3 General venting

21 Installation & Service Manual The installer must use a specific vent starter adapter at the flue collar connection, supplied by the vent m

Pagina 15 - General venting (continued)

4 Sidewall direct ventingVent/air termination – sidewallFollow instructions below when determining vent location to avoid possibility of severe perso

Pagina 16

4 Sidewall direct venting (continued)5. Maintain clearances as shown in FIG.’s 4-1A thru 4-3B, pages 22 and 23. Also maintain the following:a. V

Pagina 17

All vent pipes and air inlets must terminate at the same height to avoid possibility of severe personal injury, death, or substantial property damage.

Pagina 18

4 Sidewall direct venting (continued) Sidewall termination – optional concentric vent Description and usageThe manufacturer offers optional concentr

Pagina 19

4 Sidewall direct venting Sidewall termination – optional concentric vent models Figure 4-8 Concentric Vent Dimensional DrawingInstead of cementing t

Pagina 20

274 Sidewall direct venting (continued) Sidewall termination – optional concentric vent Multiventing sidewall terminationsWhen two (2) or more direc

Pagina 21

5 Vertical direct ventingVent/air termination – vertical ALTERNATE INTAKE LOCATIONS:INTAKE PIPES MAY BE LOCATEDANYWHERE WITHIN 24” OF VENTPIPEBIRD SC

Pagina 22 - 4 Sidewall direct venting

5 Vertical direct venting (continued) Vent/air termination – vertical 29 Installation & Service Manual Prepare roof penetrations1. Air pip

Pagina 23

Installation & Service Manual Please read before proceedingInstaller – Read all instructions, in this manual before installing. Perform ste

Pagina 24

5 Vertical direct venting Vertical termination – optional concentric vent Description and usageThe manufacturer offers an optional concentric combust

Pagina 25 - Description and usage

315 Vertical direct venting (continued) Vertical termination – optional concentric vent Figure 5-6 Concentric Vent Roof Installation Ensure termina

Pagina 26

5 Vertical direct venting Alternate vertical concentric ventingThis appliance may be installed with a concentric vent arrangement where the vent pip

Pagina 27 - 12"

Figure 5-10 Existing Vent as a ChaseFLUE EXHAUSTSEALIMG00236SEALEDCAPAIR INLETWITH SCREENSEALEXISTING5 Vertical direct venting (continued) Existing

Pagina 28 - 5 Vertical direct venting

346 Hydronic pipingSystem water piping methodsThe Cadet heating boiler is designed to function in a closed loop pressurized system not less than 12 p

Pagina 29 - Prepare roof penetrations

356 Hydronic piping (continued) Installation & Service ManualNear boiler piping components1. Boiler system piping: Boiler system piping MU

Pagina 30

366 Hydronic piping Installation & Service ManualNear boiler piping connectionsVENTAIRY-STRAINER(RECOMMENDED)DOMESTICHOT WATERPUMPCONDENSATE

Pagina 31 - CAUTION

37Near boiler piping connections (cont’d)VENTAIRY-STRAINER(RECOMMENDED)DOMESTICHOT WATERPUMPCONDENSATEDRAINSYSTEMPUMPBOILER PUMPFROM SYSTEMTO SYSTEMTO

Pagina 32

386 Hydronic piping 05101520253002468101240 Model70 Model100 Model120 ModelFLOW RATE (GPM)PRESSURE DROP (FEET OF HEAD)Figure 6-3 Pressure Drop vs. Fl

Pagina 33 - Existing vent as a chase

39Figure 6-4 Single Boiler - Primary / Secondary PipingPlease note that these illustrations are meant to show system piping concept only, the installe

Pagina 34 - 6 Hydronic piping

4The Cadet Heating Boiler - How it works...1. Heat exchanger Allows system water to flow through specially designed coils for maximum heat transfer

Pagina 35 - Hydronic piping (continued)

40Figure 6-5 Single Temperature Zoned with Circulators - DHW PriorityPlease note that these illustrations are meant to show system piping concept only

Pagina 36

416 Hydronic piping (continued) Figure 6-6 Multiple Boilers - Single Temperature Zoned with Circulators - DHW PriorityPlease note that these illustr

Pagina 37 - Circulator sizing

7 Gas connectionsConnecting gas supply piping1. Remove the front access panel and refer to FIG. 7-1 to pipe gas to the boiler. a. Install a field

Pagina 38

7 Gas connections (continued) Failure to apply pipe sealing compound as detailed in this manual can result in severe personal injury, death, or sub

Pagina 39 - DHW TANK

447 Gas connections NominalIron PipeSize (Inches)Natural Gas Pipe Capacity ChartLength of Pipe in Straight Feet for 1/2 PSI10203040506070809010012515

Pagina 40

457 Gas connections (continued)  WARNINGWhen re-tightening the set screw, be sure to tighten securely to prevent gas leaks.Do not check for gas lea

Pagina 41

8 Field wiring ELECTRICAL SHOCK HAZARD – For your safety, turn off electrical power supply before making any electrical connections to avoid possible

Pagina 42 - 7 Gas connections

478 Field wiring (continued) Outdoor temperature sensorIn accordance with the United States Energy Policy and Conservation Act, this boiler is equi

Pagina 43 - Propane Gas:

488 Field wiring COMNOSYSTEM SUPPLY SENSOR(OPTIONAL)OUTDOOR SENSOR(FACTORY SUPPLIED)TANK SENSOR(OPTIONAL)ROOM THERMOSTAT(FIELD SUPPLIED)TANK THERMOS

Pagina 44

498 Field wiring (continued) Installation & Service Manual TANK THERMOSTATROOM THERMOSTAT /ZONE CONTROLFLOW SWITCHSYSTEM SENSOROUTDOOR SEN

Pagina 45 - Gas connections (continued)

IMG002021711231027Front View IMG00204124561618192021252831263027IMG00205FRONT OFBOILER1513141821222629Right Side (inside unit) The Cadet Heating Boile

Pagina 46 - 8 Field wiring

508 Field wiring Installation & Service ManualLOW VOLTAGE CONNECTIONBOARDBOILER CONTROLMODULEBOILER PUMPDHW PUMPIGNITORBLOWERGAS VALVEDISPL

Pagina 47 - Field wiring (continued)

519 Condensate disposalCondensate drain1. This boiler is a high efficiency appliance that produces condensate.2. The bottom of the boiler has a 3/4

Pagina 48

10 Start-upCheck/control water chemistryDo not use petroleum-based cleaning or sealing compounds in the boiler system. Damage to elastomer seals and

Pagina 49 - 8 Field wiring (continued)

5310 Start-up (continued) Check for gas leaksBefore starting the boiler, and during initial operation, smell near the floor and around the boiler f

Pagina 50

5410 Start-up Final checks before starting the boiler Read this manual to familiarize yourself with boiler control module operation. Reference pa

Pagina 51 - 9 Condensate disposal

10 Start-up (continued) LBL20274 REV AFigure 10-2 Operating Instructions55 Installation & Service Manual

Pagina 52 - 10 Start-up

56Please note that the brackets ([]) denote screen status. NOTICE3. Place the boiler into the active position by pressing the UP button for five (5)

Pagina 53 - 10 Start-up (continued)

5711 Operating information GeneralHow the boiler operatesThe Cadet heating boiler uses an advanced stainless steel heat exchanger and electronic cont

Pagina 54

5811 Operating information The control monitors the temperature difference between the inlet and the outlet sensor. If this difference exceeds 55°F

Pagina 55

5911 Operating information (continued)User programming sequence Installation & Service ManualAer Timeout Base State ScreenShow Status and T

Pagina 56

6RatingsNotes:1. As an Energy Star Partner, the manufacturer has determined that Cadet heating boilers meet the Energy Star guidelines for energy eff

Pagina 57 - 11 Operating information

60Installer programming sequence Installation & Service ManualBase State ScreenShow Status and Temperatures ON/OFFPress UP for 5 seconds toei

Pagina 58

Installation & Service Manual61Parameter tableTable 11-1 This table lists boiler control module parameters and where to access themViewa

Pagina 59 - User programming sequence

6211 Operating information Installation & Service ManualAccess modesUserPress the ENTER button for 5 seconds.InstallerMost parameters are a

Pagina 60

Cadet heating boiler control moduleMODULATION INCREMENTS(20% INCREMENTS) OF FIRING CONTROLDOWN BUTTON“RESET” LOCKOUT OR “SET”FOR CHANGING SETTINGSENT

Pagina 61 - Parameter table

64Maintenance and annual startupTable 12A Service and Maintenance SchedulesService technician(see the following pages for instructions)General: • Add

Pagina 62

12 Maintenance (continued)Follow the Service and maintenance procedures given throughout this manual and in component literature shipped with the boi

Pagina 63

Check expansion tank1. Expansion tanks provide space for water to move in and out as the heating system water expands due to temperature increase or

Pagina 64 - 12 Maintenance

6712 Maintenance (continued) IMG00263BURNER DOORW/ BURNERNUTS(QTY. 4)Figure 12-2 Burner AssemblyCheck flame signal1. At high fire the flame signal s

Pagina 65 - 12 Maintenance (continued)

68The boiler contains ceramic fiber materials. Use care when handling these materials per instructions on page 67. Failure to comply could result in

Pagina 66

69 Installation & Service Manual13 TroubleshootingLabel all wires prior to disconnection when servicing controls. Wiring errors can cause i

Pagina 67

The Cadet heating boiler gas manifold and controls met safe lighting and other performance criteria when the boiler underwent tests specified in ANSI

Pagina 68

70 Installation & Service Manual 13 TroubleshootingTable 13-1 Troubleshooting Chart - No DisplayFAULT CAUSE CORRECTIVE ACTIONNo Display- No

Pagina 69 - 13 Troubleshooting

71 Installation & Service Manual13 Troubleshooting (continued)Table 13-2A - Inlet Water/System/DHW Sensor Resistance vs. TemperatureTable 13

Pagina 70

72 Installation & Service Manual13 TroubleshootingTable 13-3 Troubleshooting Chart - Noisy SystemFAULT CAUSE CORRECTIVE ACTIONNoisy Operatio

Pagina 71 - Troubleshooting (continued)

73 Installation & Service Manual13 Troubleshooting (continued)Table 13-4 Troubleshooting Chart - Fault Messages Displayed on Boiler Interfac

Pagina 72

74 Installation & Service Manual13 TroubleshootingTable 13-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed

Pagina 73

75 Installation & Service Manual13 Troubleshooting (continued)Table 13-4 (continued from previous page) Troubleshooting Chart - Fault Messag

Pagina 74

76 Installation & Service Manual13 TroubleshootingTable 13-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed

Pagina 75

77 Installation & Service Manual 13 Troubleshooting (continued)Table 13-4 (continued from previous page) Troubleshooting Chart - Fault Messa

Pagina 76

78 Installation & Service Manual 13 TroubleshootingTable 13-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displaye

Pagina 77

79 Installation & Service Manual Combustion Analysis Procedure1. Turn the main power off to the boiler.2. Remove the flue temperature senso

Pagina 78

IMG002086" MINIMUMTOP1/4" MINIMUM CLEARANCEAROUND HOT WATER PIPES24" SERVICEBOTTOM0" MINIMUMOPEN FRONT24" SERVICE6" MIN

Pagina 79

14 Combi80 Installation & Operation Manual The Cadet Combi - How it works...1. DHW pump Begins operation when the domestic flow switch enabl

Pagina 80 - 14 Combi

14 Combi (continued)81 Installation & Service Manual Maximum Domestic Water Pressure 145 PSIDomestic Water Connections 3/4" CopperFlow S

Pagina 81 - 14 Combi (continued)

14 Combi82 Installation & Service ManualDHW SENSORFLOW SWITCHIMG00261Connection Board ConfigurationsOJ1 OJ2Standard Altitude,Standard(Non-Com

Pagina 82

14 Combi (continued)83 Installation & Service ManualWater pipingField connections are to be made as represented in FIG. 14-3. WARNINGEnsure

Pagina 83

8414 Combi Installation & Service Manual Setting DHW target temperature WARNINGAn excessively high DHW temperature set point can result in

Pagina 84 - 14 Combi

8515 Diagrams24 VAC-T-T-T-T-TOUTDOORSENSORTANKSENSORSYSTEMSENSOR123456DISPLAY120VACNEUTRAL GROUND120V SUPPLY "L"120V SUPPLY "N"IN

Pagina 85 - 15 Diagrams

-T23112 453BLOWERBOX DEPICTSOPTIONAL ITEMSBOX DEPICTSDUAL SENSORSINGLE HOUSING24 VACCOM-T-T-T-THIGH VOLTAGELOW VOLTAGE120 VACHIGH VOLTAGE SPARK LEADCA

Pagina 86

24 VAC-T-T-T-T-TOUTDOORSENSORDHW OUTLETSENSORSYSTEMSENSOR123456DISPLAY120VACNEUTRAL GROUND120V SUPPLY "L"120V SUPPLY "N"INTEGRATED

Pagina 87 - 15 Diagrams (continued)

-T23112 453BLOWERNotes:1. All wiring must be installed in accordance with: local, state, provincial and national code requirements per either N.E.C.

Pagina 88

89Notes Installation & Service Manual

Pagina 89

Provide air openings to room:Cadet heating boiler alone in boiler room1. No air ventilation openings into the boiler room are needed when clearances

Pagina 90

90 Installation & Service ManualNotes

Pagina 91

91 Installation & Service ManualNotes

Pagina 92

Revision A (ECO #C10659) initial release. Revision B (ECO #C11102) reflects outdoor air reset updates along with changes made to Table 3B on page 16